FDX-A Series Emergency Lightingby IDRM FranceS.A.T.I Sel contained emergency lighting unitsII 2 GD - EEx d IIC T6 (IP66/67)Automatic testsVersions: Escape route lighting (> 45 lm)Space lighting (> 300 lm) Technical Characteristics EC type examination certificate: LCIE 97 ATEX 6012Type approved: FLdZones: 1 and 2 (Gas) - 21 and 22 (Dust)Gas and dust group: II 2 GDMarking: EEx d IIC T6Degree of protection: IP66/67 (EN 60529) T 85°CExternal mechanical impacts: IK 08 (EN 50102)Ambient temperature: -20°C +55°CPainting: RAL5018 (Blue)Material: Zamak + toughened glassWeight: 8 kgVoltage: 230 Volts (-10%, +10%) 50/60HzEquipment incorporated: Brackets suppliedThreads: 2x 3/4"NPT (1x supplied stopping plug)Connection: 2x 5x 2.5mm² terminalStandby time: 1Hr (non-permanent)Charging indicator: YesCharging time: 24Hrs On request Accessories, cable entry and stopping plugs European Union Directive 94/9/EC (March 23, 1994) – ATEX. European Union Rules EN 50014 - Explosive atmospheresEN 50018 - Flameproof enclosures EN 50281-1-1 Combustible dustEN 60598-1 - LuminairesEN 55015 - Radio interference suppressionEN 61547 - EMC Immunity